Operating & Service Instructions -for- HP7 Microprocessor Controller Includes Connection of External Controllers Dealer & Service
105) With [ELC] displayed, use the Up or Down arrow keys to select a lock code number. The factory set lock code is “17”. Not depressing any butto
11 10. Fan Speed Control… This option is not applicable to any current models. If option present, factory default setting of “80” MUST remain.
WARNING !!!! Dealer & Service Center Use Only SERVICE & SET UP FEATURES LEVEL-2 ACCESS (Includes Configuration for External Controllers) 1
WARNING !!!! Dealer & Service Center Use Only 3.2: Configuring for External Controllers not Equipped with an “OFF” Position Switch, a
WARNING !!!! Dealer & Service Center Use Only B. Remove the unit front panel to gain access to the defrost sensor . The defrost sensor will be
WARNING !!!! Dealer & Service Center Use Only 7. Changing Service Lock Code & “Backdoor” Entry… A. Changing the Code… The factory defau
WARNING !!!! Dealer & Service Center Use Only 8) [DEL] will display (At this point you have entered the service menu, and service-level program
WARNING !!!! Dealer & Service Center Use Only LEVEL-2 FAULT CODES Message Error Description Possible Cause [dPO] De
WARNING !!!! Dealer & Service Center Use Only APPENDIX Connecting to, and Configuring Microprocessor for, External Control: • A: Jandy and P
Connecting Specific Jandy Or Pentair/Compool Controllers (See application table within) Appendix- A Instructions For Connecting Specific Jandy Or Pe
Revised 10/14/03 TABLE of CONTENTS GENERAL DESCRIPTION of HP7 CONTROLLER...4 HP7 CONTROLLER SPECIF
Warning ! WARNING !!!! Dealer & Service Center Use Only MAKE CERTAIN POWER SUPPLY TO HEATPUMP and CONTROLLER IS DISCONNECTED PRIOR TO CONTIN
WARNING !!!! Dealer & Service Center Use Only Warning ! MAKE CERTAIN POWER SUPPLY TO HEATPUMP and CONTROLLER IS DISCONNECTED PRIOR TO CONTINIUI
Connecting Controllers Not Equipped With an OFF Setting (See application table within) WARNING !!!! Dealer & Service Center Use Only Appendix-
Connecting a Remote Flow Switch WARNING !!!! Dealer & Service Center Use Only Appendix- C Installing A Remote Flow Switch For Automatic Thermo
FIGURE 1FLOW SWITCH INSTALLED IN POOL RETURN LINE WARNING !!!! Dealer & Service Center Use Only SPA Return Line Installation 1. Disconnect pow
FLOW SWITCH INSTALLED IN SPA RETURN LINEFIGURE 2 WARNING !!!! Dealer & Service Center Use Only For Assistance Call AquaCal @ 800-786-7751 Mon
WARNING !!!! Dealer & Service Center Use Only Installing a Call Flex Kit Appendix- D Installing a Call Flex Kit for Time Clock Management - He
WARNING !!!! Dealer & Service Center Use Only Diagrams 27
CAUTION ! ONLY NON-ENERGIZING (“DRY”) CIRCUIT SHOULD BE CONNECTED; NEVER APPLY EXTERNAL-SOURCE VOLTAGE TO THE HP7 MICROPROCESSOR TERMINAL BOARD. FA
2737 24th Street North St. Petersburg, FL 33713 800-786-7751 www.aquacal.com 29
2. Time Delay [dEL] :...12 3. Con
GENERAL DESCRIPTION of HP7 CONTROLLER The HP7 is a powerful microprocessor control designed for use in swimming pool & spa heat pumps. Th
Control Features: ♦ Compressor Operation ♦ Refrigerant Circuit Hi & Low-Pressure Lock Out ♦ Water Pump Option (Call Flex) ♦ Precise Evapora
CONTROL PANEL SYMBOLS UNIT is HEATING WATER TEMPERATURE SET POINT ACTUAL WATER TEMPERATURE POOL SELECTION SPA SELECTION 6
SEQUENCE of OPERATION PUMP OFFPOWER ON______________________"FLO" DisplayedPUMP ONPOWER ON______________________Water Temp. DisplayedSET
8START UP & SETTING OPERATING CONTROLS LEVEL-1 (Owner) ACCESS NOTE: Covered within this section are features and settings typically accessed
9 5. Changing The Pool Temperature Set Point: A. Using the Pool / Spa key, select the POOL temperature set point. The pool set point indicator lig